Transformer electrical testing & repairs

Oil results tell you something is wrong. Electrical tests tell you where. We test windings, insulation and tap changers, then carry out the repair, from terminations to switchgear.

Medium-voltage switchgear panels with ammeters and protection relays for transformer No. 1 and No. 2

Electrical tests we carry out

Diagnostic tests give an objective picture of the windings, insulation and tap changer. Results are recorded as a baseline, so every future test can be compared against the last.

TestWhat it finds
Insulation resistance & polarisation indexMoisture, contamination and deterioration of the winding insulation, between windings and to earth.
Turns ratio (TTR)Shorted turns, open circuits and tap changer faults, by checking the ratio on every tap.
Winding resistanceLoose or high-resistance connections, broken strands and worn tap changer contacts.
Tap changer checksCorrect operation, contact condition and mechanism wear across the tap range.
Protection device checksFunction of the Buchholz relay, oil and winding temperature indicators, and pressure relief devices.

Electrical repairs and maintenance

  • Bushing inspection, cleaning and replacement
  • LV and MV cable terminations and connections
  • Tap changer servicing and repairs
  • Buchholz relays, temperature gauges and protection devices
  • Mini-substation and ring main unit (RMU) maintenance
  • MV switchgear inspection on transformer feeders
  • Testing before energising new, repaired or relocated units

Mini-substations and ring main units

On mines and industrial sites, mini-subs and RMUs often sit outdoors in dust, heat and weather for decades. We inspect, service and refurbish them, from the transformer compartment and oil to the switchgear, terminations and enclosure, and return them to service looking and working like new.

Why combine electrical and oil diagnostics?

Each test sees part of the picture. Together they find the cause.

Example: dissolved gas analysis shows rising ethylene, a sign of a thermal fault. Winding resistance testing then shows one phase reading higher on certain taps, pointing to a poor tap changer contact. The contact is repaired, the oil is purified, and a follow-up sample confirms the gases have stopped forming.

Because our team handles oil analysis, electrical testing and mechanical repairs, nothing gets lost between specialists. One team takes the problem from first symptom to verified fix.

FAQ

Electrical testing questions.

How often should transformer electrical tests be done?

Typically during major planned maintenance every few years, and whenever oil results, a protection trip or a change in operating conditions suggests a problem. Critical units justify a shorter interval.

Do you test new or relocated transformers before energising?

Yes. Before a new, repaired or relocated transformer is energised, we test it and record baseline results for future comparison.

Does electrical testing require an outage?

Yes. Diagnostic tests are done with the transformer isolated and earthed. We plan the work with your team and follow your site's isolation and permit-to-work procedures.